Innotech Genesis V4 System Manuale Utente Pagina 53

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 115
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 52
Installation Instructions for Innotech Genesis Systems
Edition 011100
3-27
Figure 3-15. MP REM Multipoint Module.
POWER and DIGITAL OUTPUTS terminals are arranged across the top edge of the
module’s main circuit board. COMMS, DIGITAL INPUTS and SENSOR inputs are
arranged along the bottom edge of the board.
Power requirements are 240Vac, ±10% at 50/60Hz. Power consumption is 7VA maximum.
The three terminals of the POWER connector block are
L = 240Vac Supply
N = Neutral
E = Earth
The DIGITAL OUPUTS (relay) terminals are listed in Table 3-17. Relay contacts are rated
at 2 Amperes.
Table 3-17. MP REM Output Relay Connections.
RELAY
COMMON
CONTACT
NOT
CONNECTED
NORMALLY
OPEN
Relay 1 DI1 C DI1 I DI1 O
Relay 2 DI2 C DI2 I DI2 O
Relay 3 DI3 C DI3 I DI3 O
Relay 4 DI4 C DI4 I DI4 O
Relay 5 DI5 C DI5 I DI5 O
SHLD
LCIOOOOIIICCC OICNE
+DI#1
-
+DI#2
-
+DI#3
-
+DI#4
-
TH1 TH2SHLD
COMMS
POWER
DIGITAL OUTPUTS
DI 1 DI 2 DI 3 DI 4 DI 5
DIGITAL INPUTS SENSOR
P+ P- C-C+
MODULE VIEWED FROM THE REAR
Vedere la pagina 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 114 115

Commenti su questo manuale

Nessun commento